MICROLENE VALIDATED ULTRA VIOLET WATER DISINFECTION SYSTEMS
Microlene UV for safe drinking water made simple
Benefits of Microlene’s UV Systems
The Davey Microlene systems come with a true 254nm Teflon® based UV sensor to continuously monitor the UV output (performance) of the system and delivers a graphical colour representation of the UV intensity provided by the system.
Based on a modular, plug and play platform, the Davey Microlene systems have the most advanced residential controller on the market with a colour user interface with a multitude of screens displaying diagnostics, status, warnings and QR codes for a link back to Davey’s website.
Davey UV water disinfection systems are a safe and effective means of eliminating harmful bacteria from drinking water supplies.
Applications- No chemicals
- No taste
- No by-products
- Impossible to overdose
Product Features
- True 254nm Teflon® based UV sensor continuously measures and displays UV output (as a %)
- Colour screen controller with Lightlock™ for protected lamp replacement, includes QR codes, full diagnostics & warnings
- “Future-proof” expandability port for future upgrades and options
- Axial flow, 316 stainless steel polished chambers, designed & manufactured to ASME pressure vessel standards.
- User friendly bayonet style lamp connector (quick ¼ turn removal with no extra tools needed)
- Reliable, industry proven, proprietary low pressure coated UV lamps with ceramic bases for durability and long life of 10,000 hours
- Constant current electronic controller in a splash proof case, fully potted ballast virtually eliminates common water damage issue
- Complies with NSF/ANSI Standard 55 for disinfection performance, Class A
- Flow restrictors built into chamber to insure maximum rated flow at 40mJ is not exceeded
- UV senor provides continuous UV monitoring
Conditions For Use
Your system will provide years of use provided the system is maintained on a regular basis as per the specifications outlined in the Owner’s Manual. For the following system to perform as tested, the following water quality parameters must be met.
Parameter | Level |
Hardness | < 120 mg/L (7 gpg) |
Iron (Fe) | < 0.3 mg/L (ppm) |
Manganese (Mn) | < 0.05 mg/L (ppm) |
Tannins | < 0.1 mg/L (ppm) |
Turbidity | < 1 NTU |
Transmittance | > 75% UVT |
Please refer to the documentation for all features and full technical specifications.
Warranty Period: Months